ToolBelt HQ

Conduit Fill: 9 #12 THHN in 1" EMT

Three complete 20-amp circuits running together in commercial installation.

Results

Fill Percentage13.9%
Max Allowed40%
StatusPASS
Conductor Area0.1197sq in
Conduit Area0.864sq in